Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 2 Installing a Cisco Nexus 7010 Chassis
Grounding the Cisco Nexus 7010 Chassis
Step 3 Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely
attached to the ground lug by attempting to pull the wire out of the crimped lug.
Step 4 Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire
lug to the grounding pad with two M4 screws.
Figure 2-6 shows the location of the grounding pads on
the front side of the chassis. Figure 2-7 shows the location on the rear of the chassis. Ensure that the
grounding lug and the grounding wire do not interfere with other device hardware or rack equipment.
Figure 2-6 Grounding Port on the Front of the Cisco Nexus 7010 Chassis
1 NRTL listed 45-degree grounding lug 2 Grounding cable with 0.75 in. of insulation stripped
from the end
187225
Grounding port