22
2.
Electrical Service Specifications
a. Gas and Steam Models Only
* AWG Stranded Wire Type...size wire as per National Electrical Code or local codes. 1/23/09
** 3-Wire is available.
b. Electric Models Only
* AWG Stranded Wire Type...size wire as per National Electrical Code or local codes. 1/23/09
** 3-Wire is available.
GAS AND STEAM
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
208 3ø 328.3 *5050
230 3ø 3 31.9 * 50 50
240 3ø 326.7 *4545
380 3ø 316.2 *2525
380 3ø 4** 16.1 * 25 25
400 3ø 4** 16.1 * 25 25
416 3ø 4** 16.0 * 25 25
440 3ø 314.4 *2020
460 3ø 313.9 *2020
480 3ø 313.9 *2020
575 3ø 311.4 *2020
ELECTRIC (126 kW)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
416 3ø 4** 191 * 300 300
460 3ø 3172 *225225