of 44
 
Storage of the battery modules:
The battery modules must be stored indoors and with their protective packaging still in place.
Ambient temperature: -15 to 40 °C
(5 to 104 °F)
Relative humidity: 25–85%
Non-condensing
Store in a place free from: vibration,
dust, direct sunlight, and moisture
Stored batteries must be recharged at regular intervals depending on the storage temperature:
Storage temperature Recharge interval
-15 to 20 °C (5 to 68°F) 9 months
20 to 30 °C (68 to 86°F) 6 months
30 to 40 °C (86 to 104 °F) 3 months
Caution: Do not store the batteries for more than 12 months.
Caution: Two persons are needed for lifting components weighing 18–32 kg (40–70 lb).
1. Holding the handle, gently lift the battery unit and pull it halfway out. A locking mechanism
prevents the battery unit from being pulled all the way out.
2. Release the locking mechanism by lifting the battery unit. Pull the battery unit completely out
while supporting it.
3. Take the replacement battery unit and push it into the system.
990–3015E-001
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
29