INSTALLATION CLEARANCES
These boilers are approved for installation on combustible ooring
in an alcove with minimum clearance to combustibles of:
TABLE 4
HW
300
HW
399
HW
420
HW
520
HW
610 & 670
TOP 28" (711.2) 32" (812.8) 24" (609.6) 24" (609.6) 24" (609.6)
SIDES 6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)
REAR 6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)
VENT 6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4)
Two inch (50.8mm) clearance is allowable from combustible
construction for hot water pipes.
Sufcient area should be provided at the front and rear of the unit
for proper servicing. Clearances of 24 inches (609.4mm) in the
rear and 48 inches (1,219mm) in the front are required by code.
In a utility room installation, the door shall be wide enough to allow
the boiler to enter or to permit the replacement of another appliance
such as a water heater.
LEVELING
Each unit should be checked after installation to be certain that it is level.
If the unit is not level, insert metal shims under the legs of the unit
to correct this condition.
SYSTEM CONNECTIONS
The system installation must conform to these instructions
and to the requirements of the local code authority having
jurisdiction. Good practice requires that all heavy piping be
supported.
VENTING
A TYPICAL BOILER INSTALLATION
FIGURE 7.
VENTING THE BOILER - STANDARD VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING
THE BOILER MUST BE FOLLOWED TO AVOID CHOKED
COMBUSTION OR RECIRCULATION OF FLUE GASES.
SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE
AND ASPHYXIATION.
TYPE B VENTING MAY BE USED WITH THESE BOILERS. ALL
LOCAL UTILITY REGULATIONS ON VENTING SHOULD BE
FOLLOWED.
For boilers for connection to gas vents or chimneys, vent sizing,
installation and termination shall be in accordance with the
current edition of the National Fuel Gas Code, ANSI Z223.1, or
CAN/CSA B149.1, Installation Codes, or applicable provisions
of the local building codes.
Vent connectors serving appliances vented by natural draft shall
not be connected into any portion of mechanical draft systems
operating under positive pressure.
The minimum distance from adjacent public walkways, adjacent
buildings, openable windows and building openings shall not be
less than those values specified in the National Fuel Gas Code,
ANSI Z223.1 and/or CAN/CSA B149.1, Installation Codes;
Stack or chimney must be a minimum height of 12" (305mm)
above the annual snow fall to prevent blockage.